V.2(42), 2020
9-25The article presents the results of research on the efficiency of the electric energy storage system in traction power supply on the example of one of the sections of JSC "Russian Railways". The results of measurements of electric values of electric rolling stock when moving along the railway section under study are considered. Based on simulation modeling, an assessment of the impact of power storage systems on the capacity of the railway section is obtained. Graphs of changes in the minimum travel interval and the minimum voltage on the current collector of an electric moving train depending on the power of the storage system, energy intensity, and threshold voltages for charge and discharge modes are constructed. An algorithm for the operation of the power storage system at a traction substation or linear device has been developed. Based on the simulation results, a graph of the degree of charge is constructed and a series characteristic is determined that allows maintaining the discharge depth at the level of no more than the specified one. Based on the results of calculations, the power, energy intensity and charging characteristics of the storage system are determined, which provide the required voltage level at the current receiver of an electric moving train within the boundaries of interstation zones. -
V.2(34), 2018
65-75The article deals with issues related to theoretical and experimental studies of operating modes of the traction power supply system. The analysis of the comparison of voltages on the tires of traction substations with uncontrolled rectifiers and tires of traction substations with converter units equipped with a system of non-contact automatic voltage regulation is shown, the differences between them are shown. The modes of operation of the active partitioning post with the point of increasing voltage have been studied in detail. As a result of research, it was found that the observation time of maximum voltage values at substation tires above the average no-load voltage level is about 5 -10% of the time of day, about 7 - 8% at active posts, and 10 - 13% at passive posts. The maximum power in the active mode of the post sectioning with the point of increasing the voltage at lower voltage in the contact network is 2.9 MW. The average amount of electricity returned to the contact network point of increase of voltage, in one case is 170 kWh. The average duration of work in active mode for one case is 8,6 minutes.