  • V.2(18), 2014
    65-69

    Model design electrical resistance concrete foundation supports contact systems

    The question of the possibility of using concrete foundations support of a contact network as earthing. The analysis of the impact of the construction of the foundation for the spreading re-sistance. The results of the calculation of spreading resistance of the anchor bolt foundation metal support on the proposed formula.
  • V.2(22), 2015
    79-87

    The power selection and placement of devicescross-reactive power compensation

    Global investment projects of JSC "Russian Railways" to increase turnover suggest an increase in the load on the existing areas of electrified railways, in connection with what is urgent problem of passing the required number of pairs of trains at railway stations. Electricity consumption in railways AC characterized by a rather high consumption of reactive power due to the specifics of electric rolling alternating current, which leads to increased levels of stress and loss of power and, consequently, reduce the energy efficiency and the potential capacity and carrying capacity of the railways. One of the least capital-intensive, and in some cases the only possible rational way to strengthen the system of traction power supply AC is the use of transverse devices for reactive power compensation. The article describes the method of determining the power and choice of accommodations in the area of ​​the railway regulated and unregulated devices transverse reactive power compensation systems, traction power supply 25 kV and 2 × 25 kV. The calculation of the input impedance of the external inductance and traction power supply, the main options for power supply circuits and sectioning traction network devices and placing transverse compensation of reactive power, check to ensure a minimum level of voltage at the pantograph of electric rolling stock. The results can be used as the design of new railway sections, and in dealing with increasing the capacity of sites in operation.