Article Title

Development of a method for calculating the rational resistance of a non-controlled reactor of a thyristor-reactor device for voltage regulation under load at traction substations

Article reference
Arzhannikov B. A. , Baeva I. A. , Tarasovskiy T. S. Development of a method for calculating the rational resistance of a non-controlled reactor of a thyristor-reactor device for voltage regulation under load at traction substations Izvestiia Transsiba – The Trans-Siberian Bulletin, 2021, no. 2(46), pp. 40 – 52.

Abstract

The drawbacks of the step-by-step automatic voltage control system under load AVC and the non-contact automatic voltage control system NAVC with the reactor switching device of the converter transformer used in the traction power supply are analyzed. The scheme of a thyristor-reactor switching device (TRSD) connected to the primary winding of the transformer is considered. A brief description of the operation of a transformer with TRSD and the procedure for calculating the symmetrical and asymmetrical external natural characteristics of a converter unit with TRSD are given. Based on the dependence of the energy indicators of the converter unit on the resistance of the uncontrolled reactor TRSD, a method is proposed for calculating the rational resistance of an uncontrolled reactor, where the power factor of the converter unit is taken as the criterion of rationality. The method includes two stages: the first is the calculation of the values of the power factor of the converter unit depending on the resistance of the uncontrolled reactor and the load current of the converter unit; the second is the determination of the average load current value of the power factor of the converter unit for each considered value of the resistance of the uncontrolled TRSD reactor and the determination of the rational for the considered external natural characteristics of the unit. In accordance with the presented methodology, the calculation of the minimum permissible and rational resistances of the uncontrolled reactor TRSD as part of a converter unit with a converter transformer TRDP-16000/10 was made. Taking into account the selected rational value of the resistance of the uncontrolled reactor TRSD, a calculation was made and the external natural characteristics of a converter unit with a TRSD and a converter transformer TRDP-16000/10 are presented. The performance check of the presented calculation method for solving the problem of choosing the rational resistance of an uncontrolled reactor was carried out on a physical model of a converter unit with a TRSD, with a 12-pulse rectifier unit, with a 30 kVA transformer and a linear primary voltage of 380 V. Comparison of experimental and calculated values showed a slight discrepancy, the permissible error was not exceeded. Determination of the resistance value of an uncontrolled reactor based on the developed methodology provides the highest values of the power factor of the converter unit.