Article Title
Decrease in number of not selective shutdownsof high-speed switchesfeeders of overhead contact system
Article reference
Gor'kin A. V.
Decrease in number of not selective shutdownsof high-speed switchesfeeders of overhead contact system Izvestiia Transsiba – The Trans-Siberian Bulletin,
2016, no. 4(28), pp. 69 – 76.
Abstract
In article possibilities of decrease in number of not selective shutdowns of high-speed switches by use of the relay - the differential shunt are described at full removal of a package of steel on a branch of smaller section. Results of experimental evaluation of the work of the relay - the differential shunt are given at full removal of a package of steel in a branch of smaller section and its trial operation. Conclusions are drawn on earlier undescribed property of the relay - the differential shunt, at full removal of a package of steel on a branch of smaller section - with increase in speed of increase of current, the considerable time lag of operation of the relay appears.