Article Title

Decrease in number of not selective shutdownsof high-speed switchesfeeders of overhead contact system

Journal: Journal of Transsib Railway Studies V.4(28), 2016
Journal thematic sections: Transport power engineering
Pages: 69-76
Authors: A. V. Gor'kin
udk: 621.331:621.311
Article reference
Gor'kin A. V. Decrease in number of not selective shutdownsof high-speed switchesfeeders of overhead contact system Izvestiia Transsiba – The Trans-Siberian Bulletin, 2016, no. 4(28), pp. 69 – 76.

Abstract

In article possibilities of decrease in number of not selective shutdowns of high-speed switches by use of the relay - the differential shunt are described at full removal of a package of steel on a branch of smaller section. Results of experimental evaluation of the work of the relay - the differential shunt are given at full removal of a package of steel in a branch of smaller section and its trial operation. Conclusions are drawn on earlier undescribed property of the relay - the differential shunt, at full removal of a package of steel on a branch of smaller section - with increase in speed of increase of current, the considerable time lag of operation of the relay appears.