Article Title

Assessment of solar radiation effect on real-power losses under load in high-temperature and self-supporting insulated wires of power lines

Journal: Journal of Transsib Railway Studies V.3(39), 2019
Journal thematic sections: Power stations and electric power systems
Pages: 134-145
Authors: E. V. Petrova
udk: 621.316.1
Article reference
Petrova E. V. Assessment of solar radiation effect on real-power losses under load in high-temperature and self-supporting insulated wires of power lines Izvestiia Transsiba – The Trans-Siberian Bulletin, 2019, no. 3(39), pp. 134 – 145.

Abstract

The use of new self-supporting insulated wires and high-temperature wires in the operation of power lines allows increasing the capacity of lines and, as a rule, reducing operational costs. An optimal utilization of the power line load capacity depends on the precise determination of the permissible current loads. The values of permissible currents and steady-state temperature are the main parameters of the line operating mode, affecting the strength and sag of the conductor. The temperature of the wire depends on weather conditions and current load. There are methods for determining the temperature and permissible currents for widely used traditional wires such as AC. They are partially outlined in the EIS (Electrical Installation Standard) and the standard of PJSC FGC UES (Federal Grid Company of Unified Energy System) of 2013. However, there is lack of studies in new types of wires. The paper considers the effect of weather conditions and load on the temperature and real-power losses in insulated and high-temperature wire, and solar radiation is under special consideration. For comparison, we present the results of calculations on traditional AC wires. The research shows that solar radiation, being taken into account, provides an increase of real-power losses of about 2 % with the given values of load and weather conditions. Calculations of permissible current values according to the developed technique for classical AC wires reveal a high coincidence with the values from PJSC FGC UES standard. The relative error is within two percent, and the proposed method is more generalized. It allows simultaneous analysis of both uninsulated and insulated wires. Due to the widespread use of self-supporting insulated wires, power industry experts can use the developed software in the design and operation of modern power lines to optimize capacity.