• Рус Русский
  • Eng English (UK)

Scientific and technical journal established by OSTU. Media registration number: ПИ № ФС77-75780 dated May 23, 2019. ISSN: 2220-4245. Subscription index in the online catalog «Subscription Press» (www.akc.ru): E28002. Subscription to the electronic version is available on the «Rucont» platform.
The journal is included in the Russian Science Citation Index and in the List of Russian Scientific Journals .

Search results

  • V.1(25), 2016
    54-60

    Method of corrosion state determining of contact system concrete poles

    The article shows that the replacement of concrete poles should be based on their actual corrosion state. Authors propose a new method for determining the corrosion state of the contact system concrete poles underground part, which allows to carry out measurements on the two poles at the same time. In this case, second pole acts as a current electrode. There is a formulas for determining the resistance of concrete, resistance and capacity of «steel - concrete» interface region. This algebraical expressions are results of the transient process analysis for the contact system poles equivalent circuit. The values of these parameters define the corrosion state pole in the underground part. Using of the proposed method will significantly reduce the time and labor costs of diagnostic procedures.
  • V.2(18), 2014
    60-65

    Calculation of magnetic field over the cable with damaged

    The paper presents a calculation of the magnetic field over the cable with damage. The cable with damage is replaced to equivalent circuit «conductor - shield». The conductor and the shield is considered as two single-wire lines, loaded on the characteristic impedance to avoid reflections. For this equivalent circuit defined sine wave signal change in the conductor and the cable shield. These results indicate that in cable fault location conductor current is significantly changed and shield current reaches the maximum value. The values of the shielding factor is determined at dif-ferent frequencies for the continuous tubular aluminum conductor and steel spiral conductor. The magnetic field is determined on the earth surface over the cable with metal shield having a «con-ductor - shield» damage taking into account the shielding factor. The results show that the module and phase of magnetic field is incremented in the cable fault location, which can be fixed on the earth surface. The results of calculation will improve the methods and hardware for cable fault lo-cation searching.
  • V.4(36), 2018
    76-86

    Automation of the calculation of the distribution of electrical quantities in the system of three conductors with account their mutual influence

    The article presents the equivalent circuit of three conductors, taking into account their mutual influence. The equivalent circuit contains the resistance and inductance of each conductor, the conductivity and the capacitance of their insulation relative to the earth, as well as the mutual inductances, conductivities and capacitances of the insulation between the conductors. The mathematical foundations of calculating the distribution of electrical quantities in the system of three conductors are considered, taking into account their mutual influence. An iterative incremental model of the software life cycle was chosen as the basis for automating this calculation, taking into account existing approaches to software development. Specific features of specialized software are specified. A structural scheme of the software complex and a block diagram of the calculation algorithm are proposed. The algorithm is based on the iterative calculation of currents and voltages for three conductors, taking into account their mutual influence. In accordance with the chosen model of the life cycle of the software, three versions of software with different functionality have been developed. This allowed us to effectively organize the processes of testing, debugging and implementation. As a result, the software complex has a window interface containing four tabs and allowing to enter the initial data for the calculation, display the results in the form of graphs and tables. For saving the results of calculations, a connection with the database has been implemented.
  • V.2(26), 2016
    78-91

    Current and potential distributions in a system of underground constructions under the stray currents influence

    The paper is devoted to the calculation of the electrical quantities distribution in the system of three conductors. The first conductor is located on the surface of a uniform soil and the other two conductors are located at depths of h and h . As result, analytic expressions of current, potential and leakage current density in the first underground construction with considering the influence of the second construction was obtained. The influence of second construction increases the value of electrical quantities in the underground construction. The analytic expressions were obtained using Fourier transform method. The analysis showed the influence of the leakage current and insulation resistance of the second construction on the electric quantities distribution in the first construction
  • V.3(27), 2016
    83-91

    Determination of the additional resistance optimal values of dc traction substation drainage unit

    The article presents a method of the additional resistance calculating of ground grid drainage unit. This work has two main objectives: development of algorithm for determining the optimal values of additional resistance and to study the possibility of reducing losses in reverse traction network through drainage unit of traction substation. The calculation is carried out with a view to ensuring the normative values of the protective potential on the grounding grid and minimize losses in the reverse traction network. The method is based on the application of the reciprocity theorem, which allows to change the direction of the currents from the source to the load on the reverse one if the system is linear. The calculation of the values of additional resistance and power loss in the reverse traction network for average current on the considered traction substation of the Western-Siberian railway. In results the selection method of optimal values for the additional resistance is offered. This method can be used for designing of traction substation grounding grid protection.
  • V.4(20), 2014
    85-92

    Calculating «steel - concrete» interface region parameters with a help of transient process analysis

    The article is about defining corrosion state of overhead structures underground part. Specially designed concrete models are used for experiments and calculations. These models are made with the fabric technology of overhead structures creation. «Steel - Concrete» interface region parameters are calculated with a help of transient process which situated when DC power supply is connected to the scheme. There is a formulas and a methodic for calculation needed parameters. In the end of the article theoretical curve is located. It exactly coincides with an experimental curve.
  • V.1(29), 2017
    99-105

    The software module of formation of the panoramic image of an internal surface of an underground part of hollow reinforced concrete support of contact network and the analysis of the recognizable inhomogeneities

    Now there is no efficient decision to estimate a corrosion condition of an underground part of reinforced concrete support of contact network which is not demanding digging of a support. This problem makes actual a task of development of a hardware and software system of definition of a corrosion condition of an underground part of reinforced concrete support of contact network. As a result of work the software module allowing to realize panoramic shooting of an internal surface of an underground part of a support, to increase quality of the received images, to carry out searching of inhomogeneities and to determine their geometrical parameters, and also to make the analysis of the found inhomogeneities. Implementation of results of work will allow to reduce time and labor costs, and also to increase efficiency of diagnostic works on support of contact network.
  • V.3(35), 2018
    111-125

    Determination of electrical quantities in the system of conductors under the influence of the dc electrified railway transport using hartley transform

    The paper deals with the influence of stray currents on underground metal structures located near the traction rail network. The paper presents a system consisting of a traction rail network, a grounding grid and two isolated underground conductors located under the stray currents influence caused by electrified railway transport. Analytical expressions for the calculation of the distribution of electrical quantities in underground structures with their mutual influence were obtained. The expressions were obtained using Hartley integral transform, which in contrast to the Fourier transform allows carrying out integral transformations only with real-valued functions. The obtained expressions allow determining the zone of dangerous influence of stray current and can be used in the design of underground structure protection.